The following section lists a summary of the changes that have been made to each standard document.
RESET Air Standard for Monitors
Summary of Updates made for the RESET Air Standard for Accredited Monitors from v2.0 to v2.1:
- "Accuracy" is now "Relative Accuracy" based on current testing methodology.
- Officially introduces Trust & Transparency Score.
- Officially introduces Alternative Pathways.
- Re-wrote introduction section.
- Added Testing Disclaimer and Limitations section..
- Cleaned up text and removed extraneous words and explanations.
Page by Page Updates
Table of Contents
- Removed “TM” from all instances of RESET
- Added “Purpose and Approach”
- Changed “RESET Air Accredited Monitor Certification” to “Accreditation Requirements and Process”
- Added "Trust & Transparency Score"
- Added "Alternative Pathways"
2.6.0 Preface
- Added context to RESET Air Projects and updated wording
- Listed out intent
2.6.1 Introduction
- New section: Explain the connection between RESET Air Standard and RESET Air Monitors
- Establish what the RESET Air Standard for Accredited Monitors defines
2.6.1.1 Purpose & Approach
- New section: Purpose and Approach
- Purpose is to establish the connectivity and performance requirements for RESET Projects
- Approach is to list out minimum requirements based on industry best practices and available technology
2.6.1.2 Typologies and Usage
- New page describing the two Typologies and how they are used
- Added Description of the two different standards (Interiors and Core & Shell)
- Added relationship between tenant and landlord
- How typologies use monitors
2.6.1.3 Monitor Types
- Updated monitor descriptions
- All monitor types can be tested and accredited
2.6.2 Monitor Requirements
- New page describing how the system works and an introduction to the basic and sensor requirements for RESET Air Accredited Monitors
2.6.2.1 Basic Requirements
- Updated Introduction text
- Removed Specifications for Grade A and Grade C monitors
2.6.2.2 Sensor Requirements Introduction
- A new page to establish the sensor requirements structure first
- Added “Sensor Type/Technology and Brand/Make”
- Updated “Measuring Range” to “Measuring Range (min)”
- Added “Measuring Range (max)” row
- Updated row numbering
- Updated “Accuracy” to “Relative Accuracy”
- Removed “Performance Check”
- Updated “Re-calibration” to “Re-calibration Capability and Auto Re-calibration”
- Terms & Descriptions
- Removed Sampling Type. Unnecessary with the way we do testing
- Added “Sensor Type/Technology and Brand/Make”
- Changed “Sensor Output Resolution” to “Output Resolution”
- Updated text for “Measuring Range (min)”
- Added “Measuring Range (max)”
- Updated “Accuracy” to “Relative Accuracy”
- Describe why relative accuracy over absolute accuracy
- Changed “Performance Check and Re-calibration” to “Calibration Capability and Auto-calibration”
2.6.2.3 Sensor Requirements - Particulate Matter 2.5 (PM2.5)
- Cleaned up text
- Removed Sampling Type. Unnecessary with the way we do testing
- Updated “Measuring Range (min)” from 1-500 to 1-300
- Added “Measuring Range (max)”, 1-500
2.6.2.4 Sensor Requirements - Carbon Dioxide (CO2)
- Cleaned up text
- Changed sensor output resolution to 1
- Updated“Measuring Range (min)” from 400-5000 to 400-4000
- Added “Measuring Range (max)”, 1-5000
- Updated Relative Accuracy range to match new measuring ranges
2.6.2.5 Sensor Requirements - Total Volatile Organic Compounds (TVOC)
- Cleaned up text
- Added references to California and Australia's definitions of TVOC for ug/m3
- Updated “Measuring Range (min)” from 150-2000 to 150-2500
- Added “Measuring Range (max)”, 1-5000
- Updated Relative Accuracy range to match new measuring ranges for ppb
- Updated“Measuring Range (min)” from 65-870 to 65-1100
- Added “Measuring Range (max)”, 1-2200
- Updated Relative Accuracy range to match new measuring ranges
2.6.2.6 Sensor Requirements - Temperature
- Cleaned up text
- Added “Measuring Range (max)”, No limit
2.6.2.7 Sensor Requirements - Relative Humidity
- Cleaned up text
- Added “Measuring Range (max)”, 1-99
2.6.3 Monitor Accreditation Process
- Additional options for testing (self testing and their TTS score)
- Tests require 5x Monitors to be placed in an occupied office-like environment with people moving around
2.6.3.1 Testing Disclaimer and Limitations
- New Section: Disclaimer and Limitations
- Include Disclaimer
- Include Limitations for:
- relative vs. absolute accuracy
- drift over time
2.6.3.2 Optional Parameters for Testing
- New Section: Optional Parameters
2.6.4 Trust & Transparency Score
- Introducing Trust & Transparency Score
- Needs to add a link to the TT Score page on the RESET Website
2.6.5 Alternative Pathway
- Introducing Alternative Pathways officially
- How to introduce new Alternative Pathways
2.6.5.1 Alternative Options to Interfacing with the RESET Cloud
- Specifies the different options and statuses for how monitors connect with the RESET Cloud
2.6.5.2 Alternative Data Output Interval
- Alternative options for data output interval
2.6.5.3 Alternative for Individual Sensor Parameters
- Alternative options for accrediting less or more sensors in a monitor